Data sheet ~ Danfoss CoolTrain ~Data sheet Danfoss CoolTrain
Description
The CoolTrainis an advanced, pre-assembled hose solution tailored for liquid cooling in data centers. Featuring a pressure independent flow control valve (PICV), it ensures efficient energy transfer and reduced pumping costs. The system connects the building's supply and return headers (technical water loop - TCS) to individual racks, with a supply line marked by a blue hose and a return line marked by a red hose.
Danfoss CoolTrainintegrates the AB-QM valve in the supply line and the AMZ motorized isolation valve in the return line, creating a compact and time-saving connection set. This design optimizes hydronic balance in direct-to-chip cooling applications with variable flow, regulated by the AB-QM pressure-independent control valve. With easy installation and robust safety features, including interlockable FD83 couplings and remote monitoring capabilities, the CoolTrainoffers reliability and energy efficiency for modern data centers.


Features & benefits
Easy Installation:
- Pre-assembled for quick setup.
- Easy coupling with FD83.
Reliable Product:
- Pressure-tested for reliability.
- Flow-validated for performance.
- Dripless connections prevent leaks.
- Cleaned to ISO4406 standards.
Digital Connectivity and Telemetry:
- Novocon actuator supports Modbus RTU & BACnet MS/TP.
- Optional NovoConEnergy temperature sensors.
- Remote commissioning and presets.
- Real-time flow and energy data.
Safety Functions:
- Interlockable couplings for security.
- Motorized isolation ball valve for shut-off.
- Alarms and failure alerts via NovoCon?S.
Energy Efficiency:
- Truly pressure independent with 100% authority for optimal control performance.
- Adjustable maximum or variable flow.
Applications
The CoolTrainunit is installed between the technical water loop (TCS) and the data rack. It is suitable for both direct to chip and rear door cooling racks.
Depending on the required cooling capacity, multiple CoolTrainunits can be connected to a single data rack.
To enable remote shut?off of the water supply to the data rack, the supply and return actuators can be connected to a controller.
The pressure?independent control valve (AB?QM) regulates the required flow to the data rack and maintains hydronic balance in the system. This pressure?independent design ensures precise, dynamic control of each data rack without being affected by pressure fluctuations in the TCS loop.
Product portfolio
表格
Length |
Coupling |
Hose |
PICV |
Isolation valves (return/supply) |
2 m / 82” |
1” FD83 |
1” EHW194 |
AB-QM DN32 HF |
AMZ-112 DN25 |
3 m / 118” |
1” FD83 |
1” EHW194 |
AB-QM DN32 HF |
AMZ-112 DN25 |
3.5 m /138” |
1” FD83 |
1” EHW194 |
AB-QM DN32 HF |
AMZ-112 DN25 |
4 m /158” |
1” FD83 |
1” EHW194 |
AB-QM DN32 HF |
AMZ-112 DN25 |
Product details
General data / Technical Specifications
表格
Technical data |
Specification |
|
Flow Qnom (100%) |
83 LPM / 22 GPM |
|
Connections |
DN25 interlockable couplings, with or without swivel adapters |
|
Available lengths |
82/118/138/158” |
2/3/3.5/4 meter (or customized length) |
Setting Range (AB-QM) (%) |
10-100 |
|
Operating Pressure |
70-520 kPa / 10-75 psi |
|
Min. Differential Pressure 1) 2) |
90 kPa / 13 psi |
|
Max. operating pressure |
10bar / 145 psi |
|
Leakage Rate Shut-off |
ISO5208 Class A (no leakage) |
|
Isolation Valves (AMZ) |
Open |
|
PICV (AB-QM) |
100% |
|
Factory Setting Connections (FD83) |
Closed |
|
Wet shipment |
The hoses are delivered filled with DowFrost LC25 |
|
Flow Medium |
25% propylene glycol-based coolant with industrial corrosion inhibitors, equivalent to DowFrost LC |
|
Operating Temperature |
15 - 65 °C / 59-149 °F |
|
Factory cleanliness standard |
ISO4406 19/18/17 (>4,6,14 microns) |
|
PICV valve 3) |
AB-QM DN 32 HF |
|
Connection (to datarack & TCS) |
Dual interlock couplings (FD83 1”) 4) |
|
Hose type |
EHW194 1” |
|
- Min. differential pressure for supply and return line to reaches at least 90% of nominal flow.
- for 3.5m / 138" length
- For more information see AB-QM datasheet.
- Refer to the Operator's Manual for details on the Danfoss HansenFD83 Coupling.
Isolation Valve Actuator: AMZ-112 DN25 5)
表格
Item |
Specification |
Power Supply |
DC 24V +10%/-15% |
Power Consumption |
nom. 2.5VA, max = 3VA |
Running Speed |
28 sec/90° |
Control Type |
3-point |
Rotation Angle |
90° |
Auxiliary Switch |
SPDT, non adjustable, activated 10° ±5° from close position |
Auxiliary Switch Max. Load |
Supply: 1.5 A, 30 VDC; Return: 2A, 30VDC |
Cable |
5 meter PVC with M12 |
Protection Class |
III according to EN 60730-1 |
Grade of Enclosure |
IP52/NEMA2 |
Approvals 6), 7) |
Low Voltage Directive 2006/95/EC; EMC-Directive 2004/10/EC; RoHS II: 2011/65/EU; EN 60730-1, EN 60730-2-14; UL60730-1, CAN/CSA E60730-1; UL 60730-2-14, CAN/CSA-E60730-2-14 |
- For more information see AMZ datasheet
- Applies to AMZ-112 DN25
- Conformity is valid with associated equipment: Power supply 24VDC Class 2
Actuator options PICV AB-QM
1. NovoConS
表格
Type |
Code No. |
NovoConS |
003Z8504 |
表格
Item |
Specification |
Speed |
3/6/12/24 s/mm |
Power Supply |
24V AC/DC |
Control Signal |
0-10V, 2-10 V, 0-20mA, 4-20mA |
Communication Protocol |
BACnet MS/TP, Modbus RTU |
Enclosure |
IP54 (IP40 if mounted upside down) |
Approvals |
Directive 2014/30/EU; EN 61000-6-3:2007 + A1:2011; EN 61000-6-1:2007; RoHS II: 2011/65/E |
2. AME 120 NLX-1
表格
Type |
Supply voltage |
Speed |
Code No. |
AME 120 NLX-1 |
24 V~ |
10 s/mm @ 60 Hz / 12 s/mm @ 50 Hz |
082H5004 |
表格
Item |
Specification |
Power Supply |
24V AC |
Control Signal |
0-10V, 0-20mA |
Feedback Signal |
Analogue, Position feedback or output signal |
Enclosure |
Type 1, IP42 |
Approvals |
USA: UL Listed, CCN XABE, File E480529; plenum use UL 2043; Canada: UL listed, CCN XABE7, File E48029; Europe: CE Mark |
Accessories
表格
Type |
Length |
Connections |
Cable material |
Code No. |
Cable NovoConDigital |
1.5 m |
bus / power |
Halogen free |
003Z8601 |
Cable NovoConDigital |
5 m |
bus / power |
Halogen free |
003Z8602 |
Cable NovoConDigital |
1 m |
actuator / actuator |
Halogen free |
003Z8608 |
Cable NovoConDigital, daisy chain |
0.5 m |
actuator / actuator |
Halogen free |
003Z8605 |
Cable NovoConDigital, daisy chain |
1.5 m |
actuator / actuator |
Halogen free |
003Z8609 |
Cable NovoConDigital, daisy chain |
10 m |
actuator / actuator |
Halogen free |
003Z8610 |
Cable NovoConI/O |
1.5 m |
actuator / free wires |
Halogen free |
003Z8612 |
Note! Cables are not included with actuator and must be ordered separately. For plenum rate cables contact Danfoss.
Note! If separate Pt1000 temperature sensors are needed, Danfoss has an array of Pt1000 sensors that can be used with NovoConS. See Danfoss Pt1000 sensors ESMT, ESM-10, ESM-11, ESMB-12, ESMC, ESMU and code no. 187F3418.
Materials
表格
Wetted Materials 1) |
|
Stainless Steel |
AISI301/AISI316L/AISI304 |
Other Metals |
Brass (CR-plated)/ Brass (Ni-plated)/ DZR brass (CW602N) |
Plastics |
PPS/PPSU/PA/PFTE |
Rubber |
EPDM/EPR |
Other Materials |
Brass (CW617N/CW614N) 2) |
- Small amount of grease and oil used for assembly.
- Wetted material not in direct flow. Chemical compatibility confirmed with ASTM1384 test to PG25.
Installation
The CoolTrainTM is intended for indoor installation. Before installation, remove the dust caps from both couplings. The CoolTrainTM is delivered pre-filled with PG25 and closed couplings. During installation, connect the couplings to their counterparts in the TCS line and data rack. Ensure that the remaining system is properly flushed and deaired prior to installation to prevent any operational issues. Once securely mounted, the couplings can be opened.
Presetting of flow
The calculated flow can be adjusted easily without using special tools. Either using digital actuator or manually turning the scale as described below.
AB-QM Setting:0=0% (10-100-)
Factory setting is 100%.
Change of presetting steps:
- Remove the blue protective cap or the mounted actuator
- Turn the pointer (clockwise to decrease) to the new setting
表格
Setting |
l/h |
l/s |
GPM |
10% |
500 |
0.139 |
2.20 |
15% |
750 |
0.208 |
3.30 |
20% |
1000 |
0.278 |
4.40 |
25% |
1250 |
0.347 |
5.50 |
30% |
1500 |
0.417 |
6.60 |
35% |
1750 |
0.486 |
7.70 |
40% |
2000 |
0.556 |
8.80 |
45% |
2250 |
0.625 |
9.90 |
50% |
2500 |
0.694 |
11.00 |
55% |
2750 |
0.764 |
12.10 |
60% |
3000 |
0.833 |
13.20 |
65% |
3250 |
0.903 |
14.30 |
70% |
3500 |
0.972 |
15.40 |
75% |
3750 |
1.042 |
16.50 |
80% |
4000 |
1.111 |
17.60 |
85% |
4250 |
1.181 |
18.70 |
90% |
4500 |
1.250 |
19.80 |
95% |
4750 |
1.319 |
20.90 |
100% |
5000 |
1.389 |
22.00 |
Tender text
Tender Specification – TCS Loop to Datarack Hose Assembly with PICV
Scope: The flow between the TCS loop and the datarack shall be controlled by a pressure independent control valve (PICV) integrated into a flexible hose assembly set.
1. Hose Assembly Set Requirements
General:
- Pre-assembled set comprising one supply line and one return line.
- Hose colour coding: Supply line: Blue; Return line: Red
- Hose material: Peroxide-cured, zinc-free synthetic EPDM rubber, reinforced with 2-ply textile.
- Connection: Identical interlockable coupling halves for both TCS loop and datarack connections.
- Coupling safety: Dual interlock design, disconnectable only via locking pin and lever handle.
- Wetted materials: Chemically compatible with PG25.
Valves & Actuators:
- Supply line to include a pressure independent control valve (PICV)
- Each line to include an motorized isolation ball valve: Full bore ball valve with actuator; 3-point control capability; Actuator running speed: < 30 seconds per 90° rotation; Position indication and manual override included.
Testing & Cleanliness:
- Delivered pressure tested.
- Cleaned to ISO 4406 standard.
- Supplied with dust caps.
2. PICV Requirements
- Automatic flow limitation function.
- Self-acting / membrane-driven design.
- Modulation capability: <1 % of set flow, independent of setting.
- Authority = 1 (100 %) at all settings.
- Linear control characteristic (adjustable to equal percentage via actuator settings).
- Flow setting scale: Percentage of flow.
- Control ratio: 1:1000.
- Test plugs for pump optimisation and flow measurement.
- Option for remote flow setting via analogue, ModBus, or BACnet through PICV actuator.
|